User manual

22 - UR4848 - User manual UR4848 - User manual - 23
RED LIGHT: waiting for programming
GREEN LIGHT: done
• Withthecontrollernotconnectedtopowersupply.
The programming module is equipped with an internal battery with an au-
tonomy of about 1000 uses (2032 button battery, replaceable).
Insert the programming module and press the programming buttons.
When writing the parameters, led turns red and on completing the proce-
dure it changes to green. It is possible to repeat the procedure without any
particular attention.
WARNING
Updating Programming module
To update the programming module values, follow the proce-
dure described on rst mode, setting display 2 to
----
so as
not to load the parameters on controller
1
.
Enter conguration and change at least one parameter.
Exit conguration. Changes are stored automatically.
1
If on activation the controller does not display
memo
it means no data have been saved on
the programming module, but it is possible to update values.
7.9 Loading default values
This procedure allows to restore factory settings of the instrument.
Press Display Do
1
PRGM
for 3 seconds
Display 1 visualizes
0.000
with 1st digit blinking,
while display 2 shows
PASS
.
2
o
Change blinking digit
and move to the next one
with .
Enter password:
9999
.
3
PRGM
to conrm
Device loads default
settings.
Turn o and restart the
instrument.
7.10 Latch on function
For use with input
Pot.1
(potentiometer 6 KΩ) and
Pot.2
(potentiometer 150
KΩ) and with linear input (0…10 V, 0...40 mV, 0/4…20 mA), it is possible to asso-
ciate start value of the scale (parameter 6
LoL.i
) to the minimum position of the
sensor and value of end scale (parameter 7
uP.L.i
) to the maximum position of
the sensor (parameter 8
Latc.
congured as
Std.
).
It is also possible to x the point in which the controller will display 0 (however
keeping the scale range between
LoL.i
and
uP.L.i
) using the “virtual zero” op-
tion by setting
u.OSt.
or
u.Oin.
in parameter 8
Latc
.
If you set
u.Oin.
the virtual zero will reset after each activation of the tool; if you
set
u.OSt.
the virtual zero remains xed once tuned.
To enable the LATCH ON function select chosen conguration for parameter
LAtc
2
.
For the calibration procedure refer to the following table:
Press Display Do
1
Exit parameters congura-
tion. Display 2 shows the
writing
LAtc
.
Place the sensor on
minimum operating value
(associated with
LoL.i.
).
2
The tuning procedure starts by exiting the conguration after changing the parameter.