30 - UR4848 - User manual UR4848 - User manual - 31
Modbus
Address
Description
Read
Only
Reset
value
1009
Relay status (0 = O, 1 = On):
Bit 0 = Relay Q1
Bit 1 = Relay Q2
Bit 2 = Reserved
Bit 3 = SSR
RO 0
1010 Heating output percentage (0-10000) RO 0
1011 Cooling output percentage (0-10000) RO 0
1012
Alarms status (0 = None, 1 = Active)
Bit 0 = Alarm 1
Bit 1 = Alarm 2
Bit 2 = Alarm 3
RO 0
1013
Manual reset: write 0 to reset all alarms.
In reading (0 = Not resettable, 1 = Resettable)
Bit 0 = Alarm 1
Bit 1 = Alarm 2
Bit 2 = Alarm 3
WO 0
1014
Error ags
Bit 0 = Eeprom writing error
Bit 1 = Eeprom reading error
Bit 2 = Cold junction error
Bit 3 = Process error (sensor)
Bit 4 = Generic error
Bit 5 = Hardware error
Bit 6 = L.B.A.O. error
Bit 7 = L.B.A.C. error
Bit 8 = Missing calibration data error
RO 0
1015 Cold junction temperature (degrees.tenths) RO -
1016
Start / Stop
0 = Controller in STOP
1 = Controller in START
R/W 0
1017
Lock conversion ON / OFF
0 = Lock conversion o
1 = Lock conversion on
R/W 0
1018
Tuning ON / OFF
0 = Tuning o
1 = Tuning on
R/W 0
1019
Automatic / manual selection
0 = Automatic
1 = Manual
R/W 0
Modbus
Address
Description
Read
Only
Reset
value
1020 T.A. current ON (Ampere with tenths) RO -
1021 T.A. current OFF (Ampere with tenths) RO
1022 OFF LINE* time (milliseconds) R/W
1023 Instant Current (Ampere) R/W 0
1024 Digital Input State R/W 0
1025
Synchronized Tuning for multizone system
0 = Tuning OFF (Normal operating of the regulator)
1 = Output command OFF
2 = Output command ON
3 = Start Tuning
4 = End Tuning and output command OFF
(Write 0 for normal operating)
R/W 0
1099
Process subjected to the visualization lter and
decimal point selection
RO
1100 Process with decimal point selection RO
1101 Setpoint 1 with decimal point selection R/W EEPROM
1102 Setpoint 2 with decimal point selection R/W EEPROM
1103 Setpoint 3 with decimal point selection R/W EEPROM
1104 Setpoint 4 with decimal point selection R/W EEPROM
1105 Alarm 1 with decimal point selection R/W EEPROM
1106 Alarm 2 with decimal point selection R/W EEPROM
1107 Alarm 3 with decimal point selection R/W EEPROM
1108 Gradient Setpoint with decimal point selection RO EEPROM
1109 Percentage heating output (0-1000) R/W 0
1110 Percentage heating output (0-100) RO 0
1111 Percentage cooling output (0-1000) RO 0
1112 Percentage cooling output (0-100) RO 0
2001 Parameter 1 R/W EEPROM
2002 Parameter 2 R/W EEPROM
2072 Parameter 72 R/W EEPROM
3000 Disabling serial control of machine** RO 0
3001 First word display 1 (ascii) R/W 0
3002 Second word display 1 (ascii) R/W 0
3003 Third word display 1 (ascii) R/W 0
*
If value is 0, control is disabled. If dierent from 0, it is the max. time that can elapse between
two pollings before the controller goes o-line. If it goes o-line, the controller returns to Stop
mode, control output is disabled but the alarms are active.
**
By writing 1 on this word, the eects of the writing are cancelled on all the Modbus addresses
from 3001 to 3022. Control therefore returns to the controller.