User manual
32 - UR4848 - User manual UR4848 - User manual - 33
Modbus
Address
Description
Read
Only
Reset
value
3004 Fourth word display 1 (ascii) R/W 0
3005 Fifth word display 1 (ascii) R/W 0
3006 Sixth word display 1 (ascii) R/W 0
3007 Seventh word display 1 (ascii) R/W 0
3008 Eighth word display 1 (ascii) R/W 0
3009 First word display 2 (ascii) R/W 0
3010 Second word display 2 (ascii) R/W 0
3011 Third word display 2 (ascii) R/W 0
3012 Fourth word display 2 (ascii) R/W 0
3013 Fifth word display 2 (ascii) R/W 0
3014 Sixth word display 2 (ascii) R/W 0
3015 Seventh word display 2 (ascii) R/W 0
3016 Eight word display 2 (ascii) R/W 0
3017
Word LED
Bit 0 = LED C1
Bit 1 = LED C2
Bit 2 = LED A1
Bit 3 = LED A2
Bit 4 = LED A3
Bit 5 = LED MAN
Bit 6 = LED TUN
Bit 7 = LED REM
R/W 0
3018
Word keys
(write 1 to command keys)
Bit 0 =
Bit 1 =
Bit 2 =
R/W 0
3019
Word serial relay
Bit 0 = Relay Q1
Bit 1 = Relay Q2
Bit 2 = Relay Q3
R/W 0
3020 Word SSR serial (0 = O, 1 = On) R/W 0
3021 Word output 0...10 V serial (0…10000) R/W 0
3022 Word output 4...20 mA serial (0…10000) R/W 0
3023
Relay state in case of o-line
(only if controlled by serial)
Bit 0 = Relay Q1
Bit 1 = Relay Q2
Bit 2 = Relay Q3
R/W 0
Modbus
Address
Description
Read
Only
Reset
value
3024
Output state SSR / 0…10 V / 4…20 mA in case
of o-line (only if controlled by serial)
(0…10000)
R/W 0
3025
Serial process. Setting parameter 54 it is possi-
ble to make averages on the remote process
R/W 0
4001 Parameter 1*** R/W EEPROM
4002 Parameter 2*** R/W EEPROM
4072 Parameter 72*** R/W EEPROM
9 Conguration
9.1 Modify Conguration Parameters
For conguration parameters see paragraph 10.
Press Display Do
1
for 3 seconds
Display 1 shows
0.000
with the 1st digit
ashing, while display 2
shows
PASS
.
2
or
Changes ashing digit
and move to the next
one using key.
Enter password:
1234
.
3
to conrm
Display 1 shows the rst
parameter and display 2
shows the value.
4
or
Slide up / down through
parameters.
5
or
Increase or decrease di-
splayed value by pressing
and an arrow key.
Enter new data which will
be saved on releasing the
keys. To change another
parameter return to point 4.
6
+
simultaneously
End of conguration
parameter change.
The controller exits from
programming.
*** Parameters modied using serial address 4001 to 4072 will be stored on eeprom only after
10” since last writing of one parameter.