User manual
34 - UR4848 - User manual UR4848 - User manual - 35
10 Table of Conguration Parameters
The following table includes all parameters. Some of them will not be visible on
the models which are not provided with relevant Hardware data.
1 C.out Command Output:
Command output type selection.
c. o1
Default (necessary for using process and setpoint retransmission
function with Volt / mA output)
c. o2
c.SSr
c.uAL.
c.4.20
c.0.20
c.0.10
UR484802
COMMAND ALARM 1
c. o1
Q1 Q2
c. o2
Q2 Q1
c.SSr
SSR Q1
c.uAL.
Q1 (opens) / Q2 (closes) -
c.4.20
4 ... 20 mA Q1
c.0.20
0 ... 20 mA Q1
c.0.10
0 ... 10 mV Q1
UR484803
COMMAND ALARM 1 ALARM 2
c. o1
Q1 Q2 SSR
c. o2
Q2 Q1 SSR
c.SSr
SSR Q1 Q2
c.uAL.
Q1 (opens) / Q2 (closes) SSR -
c.4.20
4 ... 20 mA Q1 Q2
c.0.20
0 ... 20 mA Q1 Q2
c.0.10
0 ... 10 mV Q1 Q2
UR484804
COMMAND ALARM 1 ALARM 2 ALARM 3
c. o1
Q1 Q2 Q3 SSR
c. o2
Q2 Q1 SSR SSR
c.SSr
SSR Q1 Q2 Q3
c.uAL.
Q1 (opens) / Q2 (closes) Q1 SSR -
c.4.20
4 ... 20 mA Q1 Q2 Q3
c.0.20
0 ... 20 mA Q1 Q2 Q3
c.0.10
0 ... 10 mV Q1 Q2 Q3
2
SEN.
Sensor
Analogue input conguration/sensor selection
Tc.K
Tc-K (Default) -260 °C ... 1360 °C
Tc.s
Tc-S -40 °C ... 1760 °C
Tc.r
Tc-R -40 °C ... 1760 °C
Tc.j
Tc-J -200 °C ... 1200 °C
Pt
Pt100 -200 °C ... 600 °C
Pt1
Pt100 -200 °C ... 140 °C
ni
NI100 -60 °C ... 180 °C
ntc
NTC10K -40 °C ... 125 °C
Ptc
PTC1K -50 °C ... 150 °C
Pts
Pt500 -100 °C ... 600 °C
Pt1k
Pt1000 -100 °C ... 600 °C
0.10
0 ... 10 Volt
0.20
0 ... 20 mA
4.20
4 ... 20 mA
0.40
0 ... 40 mVolt
Pot.1
Potentiometer max 6 Kohm (See paragraph 7.10)
Pot.2
Potentiometer max 150 Kohm (See paragraph 7.10)
t.A.
50 mA secondary Current transformer (Only UR484803/04)
3
d.P.
Decimal Point
Select type of visualized decimal point
0
Default
0.0
1 Decimal
0.00
2 Decimal
0.000
3 Decimal