ui.tY.
Visualization Type
Select visualization for display 1 and 2
1.p.2.s.
1 Process, 2 Setpoint (Default)
1.p.2.H.
1 Process, 2 Hide after 3 sec.
1.s.2.P.
1 Setpoint, 2 Process
1.s.2.H.
1 Setpoint, 2 Hide after 3 sec.
1.p.2.a.
1 Process, 2 Ampere (T.A. input)
1.p2.0
1 Process, 2 Command output percentage
66
deGr.
Degree
Select degree type
c
Centigrade (Default)
f
Fahrenheit
67
retr.
Retransmission
Retransmission for output 0-10 V or 4…20 mA (select Jumpers JP5,
JP7 and JP9). Parameters 68 and 69 dene the lower and upper
limits of the scale.
dis.
Disabled
uo. p.
Retransmits process in Volt
ma. p.
Retransmits process in mA
uo. c.
Retransmits command setpoint in Volt
ma. c.
Retransmits command setpoint in mA
uo.o.p.
Volt output percentage
ma.o.p.
mA output percentage
uo.a.1
Volt alarm 1 setpoint
ma.a.1
mA alarm 1 setpoint
uo.a.2
Volt alarm 2 setpoint
ma.a.2
mA alarm 2 setpoint
uo.t.a.
Volt T.A.
ma.t.a.
mA T.A.
68
Lo.L.r.
Lower Limit Retransmission
Output V / mA retransmission lower limit range
-999…+9999 [digit
12
] (degrees.tenths for temperature sensors),
Default: 0.
69
up.L.r.
Upper Limit Retransmission
Output V / mA retransmission upper limit range
-999…+9999 [digit
12
] (
degrees.tenths for temperature sensors
),
Default: 1000.
70
bd.rt.
Baud Rate
Selects baud rate for serial communication
4.8 k
4.800 Bit/s
9.6 k
9.600 Bit/s
19.2k
19.200 Bit/s (Default)
28.8k
28.800 Bit/s
39.4k
39.400 Bit/s
57.6k
57. 600 Bit /s
71
sL.ad.
Slave Address
Selects slave address for serial communication
1 – 254. Default: 254
72
se.de.
Serial Delay
Select serial delay
0 – 100 milliseconds. Default: 20
73
L.L.o.p.
Lower Limit Output Percentage
Selects min. value for command output percentage
0 – 100%, Default: 0%.
Ex: with
c.out
selected as 0...10 V and
L.L.o.P.
set at 10%, command
output can change from a min. of 1 V to a max. of 10 V.
12
The display of the decimal point depends on the setting of parameter
sen.
and the parame-
ter
d.p.