12 Table of Anomaly Signals
If installation malfunctions, controller will switch o regulation output and will
report the anomaly. For example, controller will report failure of a connected
thermocouple visualizing
e -05
ashing on display for other signals, see table
below.
Cause what to do
E-01
SYS.E
Error in EEPROM cell
programming.
Call Assistance.
E-02
SYS.E
Cold junction sensor fault or
room temperature outside of
allowed limits.
Call Assistance.
E-04
SYS.E
Incorrect conguration data.
Possible loss of calibration
values.
Check if the conguration
parameters are correct.
E-05
SYS.E
Thermocouple open or tem-
perature outside of limits.
Check the connection with the
sensors and their integrity.
E-08
SYS.E
Missing calibration data. Call Assistance.
13 Summary of Conguration parameters
Date: Model UR4848:
Installer: System:
Notes:
c.oUT
Command output type selection
sen.
Analogue input conguration
d.p.
Number of decimal points
LoL.s.
Lower limit setpoint
up.L.s.
Upper limit setpoint
Lo.L.i.
Lower limit range AN1 only for linear
up.L.i.
Upper limit range AN1 only for linear
Latc
Automatic setting of linear input limits
o.cAL.
Oset calibration
G.cAL.
Gain calibration
act.t.
Regulation type
c. re.
Command output reset type
c. se.
Contact state for command output in case of error
c. Ld.
Dene the OUT1 led state
c. Hy.
Hysteresis in ON / OFF or dead band in P.I.D.
c. de.
Command delay
c. s.p.
Command setpoint protection
p.b.
Proportional band
t.i.
Integral time
t.d.
Derivative time
t.c.
Cycle time
o.poL.
Upper limit of heating output percentage
AL. 1
Alarm 1 selection
A.1.s.o.
Alarm 1 output contact and intervention type
a1.re.
Reset type of alarm 1 contact
a.1.s.e.
State of contact for alarm 1 output
a.1.Ld.
State of OUT2 led