7. 2 Auto-Tuning
Tuning procedure calculates the controller parameters and can be manual or
automatic according to selection on parameter 57 (
tunE
).
7. 3 Manual Tuning
Manual procedure allows the user greater exibility to decide when to update
P.I.D. algorithm work parameters. The procedure can be activated in two ways:
• RunningTuningbykeyboard:
Press
SET
key until display 1 shows the writing
tunE
with display 2 showing
off
, press , display 2 shows
on
.
TUN led switches on and the procedure begins.
•RunningTuningbydigitalinput:
Select
tune
on parameter 61
d G t .i .
At rst activation of digital input
(commutation on front panel) TUN led switches on and at second activation
switches o.
7.4 Automatic Tuning
Automatic tuning activates when the controller is switched on or when the
setpoint is modied to a value over 35%.
To avoid an overshoot, the treshold where the controller calculates new P.I.D.
parameters is determined by the setpoint value minus the “Set Deviation Tune”
(see parameter 58
S.D. tu .
).
To exit Tuning and keep P.I.D. values unchanged, press
SET
key until display 1
shows the writing
tune
and display 2 shows
on
. Press , display 2 shows
off
.
TUN
led switches o and procedure nishes.
7. 5 Soft-Start
To reach the setpoint the controller can follow a gradient expressed in units
(example: Degree/Hours).
Enter the gradient on parameter 62
GrAd .
with chosen Units/Hours; only on
subsequent activation the controller uses Soft-Start function.