User manual

URDR0001 - User manual - 19
If parameter 59
op.mo.
is set on
co n t.
and parameter 63
m a . ti .
is dierent from
0, after switch-on and elapsing of the time set on parameter 63, setpoint does not
follow the gradient anymore, but it reaches nal setpoint with maximum power.
Autotuning does not work when Soft-Start is activated: otherwise if parameter
63
m a . ti .
is dierent from 0 and parameter 57
tune
is set on
auto
, Autotuning
starts when Soft-Start time is nished.
If parameter 57
tune
is set on
man.
, the Autotuning can be started only when
Soft-Start nishes.
7.6 Automatic / Manual Regulation for % Output
Control
This function allows to select automatic functioning or manual command of the
output percentage.
With parameter 60
Au.ma.
, can select two methods.
1 First selection (
en.
)
Pressing
SET
key display 1 shows
p.---
, while display 2 shows
Auto
.
Pressing
key display shows
Man.
; it is now possible to change the output
percentage using
and . To return to automatic mode, using the same
procedure, select
Auto
on display 2: led MAN switches o and functioning
returns to automatic mode.
2 Second selection (
EN.ST,
)
enables the same functioning, but with two important variants:
• Ifthereisatemporarypowerfailureorafterswitch-o,themanualfunctioning
as well as the previous output percentage value will be maintained at restarting.
• If the sensor breaks during automatic functioning, the controller moves to
manual mode while maintaining the output percentage command unchanged
as generated by the P.I.D. immediately before breakage.