User manual

22 - URDR0001 - User manual
• Withthecontrollernotconnectedtopowersupply.
The memory card is equipped with an internal battery with an autonomy of
about 1000 uses (2032 button battery, replaceable).
Insert the memory card and press the programming buttons.
When writing the parameters, led turns red and on completing the procedure it
changes to green. It is possible to repeat the procedure without any particular
attention.
WARNING
Updating Programming Module
To update the memory card values, follow the procedure descri-
bed on rst mode, setting display 2 to
----
so as not to load the
parameters on controller
1
.
Enter conguration and change at least one parameter.
Exit conguration. Changes are stored automatically.
7.9 Loading default values
This procedure allows to restore factory settings of the instrument.
Press Display Do
1
SET
for 3 seconds
Display 1 visualizes
0.000
with 1st digit blinking, while
display 2 shows
PASS
.
2
o
Change blinking digit and
move to the next one with
SET
.
Enter password:
9999
.
3
SET
to conrm
Device loads default settings.
Turn o and restart
the instrument.
1
If on activation the controller does not display
memo
it means no data have been saved
on the Programming module, but it is possible to update values.