7.11 LoopBreakAlarmOnCurrentTrasformer
This function allows to measure load current and to manage an alarm during
malfunctioning (with power in short circuit or always o).
The current transformer connected to terminals 15 and 16 must be 50 mA (sam-
pling time 80 ms).
• SetendscalevalueofthecurrenttransformerinAmperesonparameter47
t.a.
• SettheinterventionthresholdoftheLoopBreakAlarminAmperesonparame-
ter 48
L.b.a.t.
• Set the intervention delay time of the Loop Break Alarm on parameter 49
L.b.a.d.
• Itispossibletoassociatethealarmwitharelaybysettingtheparameter
AL. 1
and
AL. 2
as
L.b.a.
If a remote control switch or SSR remains closed, controller signals the fault by
showing
L.b.a.c.
on display 2 (alternatively with a command setpoint).