User manual
26 - URDR0001 - User manual
• Parameter61
d G t .i .
NB: Settings on this parameter are available only if
co n t.
or
p r. cY .
are selected
on parameter 59
op.mo.
st.st.
: Start / Stop; operating on digital input the controller switches alterna-
tively from start to stop;
rn.n.o.
: Run N.O. Controller is in start only with closed input;
rn.n.c.
: Run N.C. Controller is in start only with open input;
L.c.n.o.
: With closed input allows to lock the reading of sensors;
Lc. n . c.
: With open input allows to lock the reading of sensors;
tune
: Enables / disables Tuning function if parameter 57
tune
is selected as
man.
;
a.ma.i.
: If parameter 60
au.ma.
is selected as
en.
or
en .st.
controller switch
from automatic to manual functioning;
a.ma.c.
: If parameter 60
au.ma.
is selected as
en.
or
en .st.
URDR works in
automatic mode if input is open or in manual mode if input is closed.
7.13 Dual Action Heating-Cooling
URDR is suitable also for systems requiring a combined heating-cooling action.
Command output must be congured as Heating P.I.D. (
Act. t.
=
HEAT
and
with a
P. b .
greater than 0), and one of the alarms (
A L .1
,
AL. 2
or
AL. 3
) must be
congured as
co o L.
Command output must be connected to the actuator responsible for heat, while
the alarm will control cooling action.
Parameters to congure for the Heating P.I.D. are:
Act. t.
=
HEAT
Command output type (Heating);
P. b .
: Heating proportional band;
t.i
: Integral time heating and cooling;
t.d.
: Derivative time heating and cooling;
t. c.
: Heating time cycle.