User manual
URDR0001 - User manual - 31
Modbus
Address
Description
Read
Only
Reset
value
1014
Error ags
Bit 0 = Eeprom writing error
Bit 1 = Eeprom reading error
Bit 2 = Cold junction error
Bit 3 = Process error (sensor)
Bit 4 = Generic error
Bit 5 = Hardware error
Bit 6 = L.B.A.O. error
Bit 7 = L.B.A.C. error
Bit 8 = Missing calibration data error
RO 0
1015 Cold junction temperature (degrees.tenths) RO -
1016
Start / Stop
0 = Controller in STOP
1 = Controller in START
R/W 0
1017
Lock conversion ON / OFF
0 = Lock conversion o
1 = Lock conversion on
R/W 0
1018
Tuning ON / OFF
0 = Tuning o
1 = Tuning on
R/W 0
1019
Automatic / manual selection
0 = Automatic
1 = Manual
R/W 0
1020 T.A. current ON (Ampere with tenths) RO -
1021 T.A. current OFF (Ampere with tenths) RO
1022 OFF LINE* time (milliseconds) R/W
* I
f value is 0, the control is disabled. If dierent from 0, it is the max. time which can
elapse between two pollings before the controller goes o-line. If it goes o-line, the
controller returns to Stop mode, the control output is disabled but the alarms are active.