Modbus
Address
Description
Read
Only
Reset
value
1023 Instant Current (Ampere) R/W 0
1024 Digital Input State R/W 0
1025
Synchronized Tuning for multizone system
0 = Tuning OFF (Normal operating of the regulator)
1 = Output command OFF
2 = Output command ON
3 = Start Tuning
4 = End Tuning and output command OFF
(Write 0 for normal operating)
R/W 0
1099
Process subjected to the visualization lter and
decimal point selection
RO
110 0 Process with decimal point selection RO
1101 Setpoint 1 with decimal point selection R/W EEPROM
1102 Setpoint 2 with decimal point selection R/W EEPROM
1103 Setpoint 3 with decimal point selection R/W EEPROM
110 4 Setpoint 4 with decimal point selection R/W EEPROM
1105 Alarm 1 with decimal point selection R/W EEPROM
1106 Alarm 2 with decimal point selection R/W EEPROM
1108 Gradient Setpoint with decimal point selection RO EEPROM
1109 Percentage heating output (0-1000) R/W 0
1110 Percentage heating output (0-100) RO 0
1111 Percentage cooling output (0-1000) RO 0
1112 Percentage cooling output (0-100) RO 0
2001 Parameter 1 R/W EEPROM
2002 Parameter 2 R/W EEPROM
2072 Parameter 72 R/W EEPROM
3000 Disabling serial control of machine** RO 0
**
By writing 1 on this word, the eects of the writing are cancelled on all the Modbus
addresses from 3001 to 3022. Control therefore returns to the controller.