User manual

38 - URDR0001 - User manual
4 Lo .L.S. Lower Limit Setpoint
Lower limit selectable for setpoint
-999+9999 [digit
3
] (degrees.tenths for temperature sensors),
Default: 0.
5 u p.L.S. Upper Limit Setpoint
Upper limit selectable for setpoint
-999+9999 [digit3] (degrees.tenths for temperature sensors),
Default: 1750.
6 Lo L.i Lower Linear Input
Range AN1 lower limit only for linear. Example: with input 4...20 mA
this parameter takes value associated to 4 mA
-999 bis +9999 [digit
3
], Default: 0.
7 u p.L.i . Upper Linear Input
Range AN1 upper limit only for linear. Example: with input 4...20
mA this parameter takes value associated to 20 mA
-999 bis +9999 [digit
3
], Default: 1000.
8 La t c. Latch On Function
Automatic setting of limits for linear inputs and potentiometers
(see paragraph 7.10)
di s .
Disabled (Default)
std .
Standard
u.0st.
Virtual zero stored
u . 0i n
Virtual zero initialized