18 p. b . Proportional Band
Proportional band Process inertia in units (ex: if temperature is in °C)
0 ON / OFF
t.i .
if equal to 0 (Default)
1-9999 [digit
3
] (degrees.tenths for temperature sensors)
19 t . i . Integral Time
Process inertia in seconds
0.0-999.9 seconds (0 = integral disabled), Default: 0.
20 t. d . Derivative Time
Normally ¼ of integral time
0.0-999.9 seconds (0 = derivative disabled), Default: 0.
21
t. c. Cycle Time
Cycle time (for P.I.D. on remote control switch 10 / 15 sec., for
P.I.D. on SSR 1 sec.) or servo time (value declared by servo-motor
manufacturer)
1-300 seconds, Default: 10.
22 o .Po L. Output Power Limit
Selects max value for command output percentage.
0-100%, De-
fault
: 100%.
3
Display of decimal point depends on setting of parameter
sen.
and parameter
d. p.