25 a1 . r e . Alarm 1 Reset
Alarm 1 contact reset type
a re.
Automatic reset (Default)
m re.
Manual reset
SET
m re.s.
Manual reset stored. (keeps relay status also after an even-
tual power failure)
26
a .1 . s . e . Alarm 1 State Reset
State of contact for alarm 1 output in case of error
c. o .
Open contact (Default)
c. c.
Closed contact
27 a.1.Ld. Alarm 1 Led
Denes the state of OUT2 led corresponding to the relative contact
c. o .
ON with open contact
c. c.
ON with closed contact (Default)
28 a .1 . H y . Alarm 1 Hysteresis
-999+999 [digit
5
] (degrees.tenths for temperature sensors), Default:
0.0.
29
a .1 . d e . Alarm 1 Delay
-180…+180 seconds. Negative: delay in alarm output phase.
Positive: delay in alarm entry phase. Default: 0.
5
Display of decimal point depends on setting of parameter
sen.
and parameter
d. p.