33 A2. re. Alarm 2 Reset
Alarm 2 contact reset type
Are.
Automatic reset (Default)
m re.
Manual reset (reset / manual reset by keyboard)
SET
m re.s.
Manual reset stored. (keeps relay status also after an even-
tual power failure)
34
a .2. s . e. Alarm 2 State Error
State of contact for alarm 2 output in case of error
c. o .
Open contact (Default)
c. c.
Closed contact
35 a.2.Ld . Alarm 2 Led
State of OUT2 led corresponding to relative contact
c. o .
ON with open contact
c. c.
ON with closed contact (Default)
36 a .2.HY. Alarm 2 Hysteresis
-999+999 [digit
7
] (degrees.tenths for temperature sensors), De-
fault
: 0.0.
37 a.2.d.e. Alarm 2 Delay
-180…+180 seconds. Negative: delay in alarm exit phase.
Positive: delay in alarm entry phase. Default: 0.
7
Display of decimal point depends on setting of parameter
sen.
and parameter
d. p.