User manual

46 - URDR0001 - User manual
38 a . 2 . s . p . Alarm 2 Setpoint Protection
Alarm 2 set protection. Does not allow operator to change value set
free
Modication allowed (Default)
Lo ck
Protected
Hi d e
Protected and not visualized
47 t.a. Current Transformer
Activation and scale range of current transformer
0 Disabled. 1-200 Ampere. Default: 0
48 L.b.a.t. Loop Break Alarm Threshold
Intervention threshold of Loop Break Alarm
0.0-200.0 Ampere. Default: 50.0
49 L.b.a.d. Loop Break Alarm Delay
Delay time for Loop break alarm intervention
00.00-60.00 mm.ss. Default: 01.00
50 co o . f. Cooling Fluid
Type of refrigerant uid for heating / cooling P.I.D.
Ai r
Air (Default)
oi L
Oil
H2o
Water
51 p.b.m. Proportional Band Multiplier
Proportional band multiplier. Proportional band for cooling action
is given by parameter 18 multiplied for this parameter.
1.00-5.00
(
Default: 1.00)