User manual

URDR0001 - User manual - 47
52 ou.d.b. Overlap / Dead Band
Dead band combination for heating / cooling action in heating /
cooling P.I.D. mode (dual action).
-20.0-50.0% of proportional band value (Default: 0).
Negative indicates dead band value. Positive means overlap.
53
co.t.c. Cooling Cycle Time
Cycle time for cooling output
1-300 seconds, Default: 10.
54 c. fLt. Conversion Filter
ADC Filter: Number of input sensor readings to calculate the mean
that denes process value. NB: When readings increase, control
loop speed slows down
di s .
Disabled
2. s. m .
2 Samples Mean
3. s . m .
3 Samples Mean
4. s . m .
4 Samples Mean
5. s . m .
5 Samples Mean
6. s. m.
6 Samples Mean
7. s. m.
7 Samples Mean
8. s . m.
8 Samples Mean
9. s . m .
9 Samples Mean
10.s . m.
10 Samples Mean (Default)
11 . s . m .
11 Samples Mean
12. s . m .
12 Samples Mean
13.s . m .
13 Samples Mean
14.s. m .
14 Samples Mean
15.s . m .
15 Samples Mean