69 up.L.r. Upper Limit Retransmission
Output V / mA retransmission upper limit range
-999+9999 [digit
9
] (degrees.tenths for temperature sensors), Default:
1000.
70 bd . rt. Baud Rate
Selects baud rate for serial communication
4.8 k
4.800 Bit/s
9.6 k
9.600 Bit/s
19.2k
19.200 Bit/s (Default)
28.8k
28.800 Bit/s
39.4 k
39.400 Bit/s
57.6k
57.6 00 B it/s
71
sL. a d . Slave Address
Selects slave address for serial communication.
1 – 254, Default: 254
72 se. d e. Serial Delay
Select serial delay.
0 – 100 milliseconds. Default: 20
73 L. L. o . p. Lower Limit Output Percentage
Selects min. value for command output percentage
0 – 100%, Default: 0%.
Ex: with
c.out
selected as 0...10 V and
L.L. o .P.
set at 10%, command
output can change from a min. of 1 V to a max. of 10 V.
9
The display of the decimal point depends on the setting of parameter
sen.
and the
parameter
d. p.