  PUREHEAT™ HYDRONIC AIR HEATER OPERATOR’S MANUAL – SECTION 2 
2- 2  © 2006 Ground Heaters, Inc.  V. 2, Rev. 09/01/06   
2.1.1.5 HX50 Heat Xchangers™
  A Pureheat™ Hydronic Air Heater equipped with HX50 Heat Xchangers
TM
 and 4-Port Remote Manifolds 
should conform to the following system configurations: 
•  Connect the Four (4) 4-Port Remote Manifolds utilizing any combination [50 ft (15 m) or 100 
ft (30 m)] of Circulation Hoses with a maximum overall horizontal run not to exceed 150 ft 
(45 m) for each 4-Port Remote Manifold. 
•  The maximum vertical rise or drop from the Pureheat to each Xchanger
TM
 or 4-Port Remote 
Manifolds is 60 ft one way from base unit. 
•  Connect Four (4) HX50 Heat Xchangers
TM
 to each of the Four (4) 4-Port Remote 
Manifolds utilizing the 40 ft (12 m) 1/2 in. ID Black Circulation Hoses mounted on the 
HX50 Heat Xchangers
TM
. 
2.1.1.6 HX50 Heat Xchangers™ with Booster Pump
  A Pureheat™ Air Heater equipped with the HX50 Heat Xchangers™, 4-Port Remote Manifolds, optional 
Booster Pump and Auxiliary Pump Panel should conform to the following system configurations: 
•  Connect the Four (4) 4-Port Remote Manifolds utilizing any combination [50 ft (15 m), 100 ft 
(30 m) or 200 ft (61 m)] of Circulation Hoses with a maximum overall horizontal run not to 
exceed 350 ft (106 m) for each 4-Port Remote Manifold. 
•  The maximum vertical rise or drop from the Pureheat to each Xchanger
TM
 or 4-Port Remote 
Manifold is 100 ft (30 m) one way from base unit. 
• Connect the Four (4) HX50 Heat Xchangers
TM
 to each of the Four (4) 4-Port Remote 
Manifolds utilizing the 40 ft (12 m) 1/2 in. ID Black Circulation Hoses mounted on the 
HX50 Heat Xchangers
TM
. 
2.1.1.7 Maximum Heat Xchanger™ Connection Capability
  Connecting the maximum number of Heat Xchangers™ will
 not increase the heat delivered to the space 
(compared to above stated standard configurations) but will provide increased air circulation. 
All Pureheat™ Hydronic Air Heaters are equipped with a 5-Port On-Board Manifold (Circulation Hoses 
connection points) capable of a maximum connection of five (5) HX200 Heat Xchangers™, ten (10) 
HX100 Heat Xchangers™ with Five (5) 4-Port Remote Manifolds, and twenty (20) HX50 Heat 
Xchangers™ with Five (5) 4-Port Remote Manifolds. 
2.1.2  Optional Booster Pump 
All Pureheat™ Hydronic Air Heaters are equipped to accept an optional Booster Pump which requires the 
use of an Auxiliary Pump Panel for electrical connection to provide safety shutdown of the optional 
Booster Pump. (For setup instructions, refer to Section 2.8, CONNECTING/DISCONNECTING 
OPTIONAL BOOSTER PUMP.) 
2.1.3  Circulation Hose Limitations
 Do not
 create excessively long Circulation Hoses by connecting multiple (more than two) Circulation 
Hoses in series. Multiple QCs cause a loss of working pressure and restrict flow. 
•  Regardless of length, no more than two (2) Supply Circulation Hoses should be connected in 
series; 
•  Regardless of length, no more than two (2) Return Circulation Hoses should be connected in 
series; 
•  Overall Supply and
 Return Circulation Hoses should be no more than a combined 400 ft (122 m) 
in length (with Main Pump); 
•  Overall Supply and
 Return Circulation Hoses should be no more than a combined 800 ft (244 m) 
in length (with optional Booster Pump); 