765-4102/0100-0000Diagnostics
132 Product manual | Version: 2.1.0
8PORT IOL-B FLD PN DC 24V 2.0A
Table 84: General Alarms
Number
(hex)
Alarm Description Corrective Action
0x0101 Overvoltage, 1L Overvoltage in supply cable 1L
The supply cable has exceeded the limiting
value for the maximum voltage
Check supply voltage
0x0102 Overtemperature Overtemperature
The device temperature has exceeded the
upper limiting value
Eliminate external heat
source or overload
0x0103 Overload, 1L Overload in supply cable 1L
The total current in supply cable 1L has ex-
ceeded the upper limiting value
Eliminate overload
0x0104 Overload, 2L Overload in supply cable 2L
The total current in supply cable 1L has ex-
ceeded the upper limiting value
Eliminate overload
0x0105 Undertemperature Undertemperature
The device temperature has fallen below
the lower limiting value
Thermally insulate the de-
vice
0x0106 Undervoltage, 2L Undervoltage in supply cable 2L
The power supply for supply cable 2L has
fallen below the limiting value for the mini-
mum voltage
Check supply voltage
0x0107 Overvoltage, 2L Overvoltage in supply cable 2L
The power supply for supply cable 2L has
exceeded the limiting value for the maxi-
mum voltage
Check supply voltage
0x0108 Forcing operating mode
active
Forcing operating mode active (activated
by Web client or OPC UA client)
The Web client or OPC UA
client should exit forcing op-
erating mode as soon as
forcing is no longer needed
0x0109 Short circuit on pin 4 Short circuit detected on pin 4 Eliminate short circuit
0x010A Short circuit on pin 2 Short circuit detected on pin 2 Eliminate short circuit
0x010B Short circuit on pin 1 Short circuit detected on pin 1 Eliminate short circuit
Diagnostic Alarms
Diagnostic alarms originate from the IO-Link master. They indicate events on the IO-Link
master or its ports. The following values are set in the “Event Qualifier”:
TYPE = 2 (Warning) or 3 (Error)
MODE = 2 (Event disappears) or 3 (Event appears)
SOURCE = 1 (Master/local)
The IO-Link master sends this event to the IO controller as a diagnostic alarm. The value
of “Channel Error (PROFINET)” is 0x9502.
The following table lists the numbers of the IO-Link master diagnostic alarms.
Table 85: IO-Link Master Diagnostic Alarms
Channel Error Extended Chan-
nel Error Type
Description Corrective Action
0x9502 0x17FF Process data error Check submodule configuration
0x9502 0x1800 No device access / loss of commu-
nication
Check IO-Link port
0x9502 0x1801 Start parameter error Check parameters