765-4102/0100-0000 Diagnostics
Product manual | Version: 2.1.0 133
8PORT IOL-B FLD PN DC 24V 2.0A
Table 85: IO-Link Master Diagnostic Alarms
Channel Error Extended Chan-
nel Error Type
Description Corrective Action
0x9502 0x1802 Incorrect device identification Check port configuration parame-
ters
0x9502 0x1803 Incorrect device identification Check port configuration parame-
ters
0x9502 0x1804 Short circuit on C/Q Check wiring
0x9502 0x1805 PHY overtemperature Check temperature and load
0x9502 0x1806 Short circuit on L+ Check wiring
0x9502 0x1807 Overcurrent on L+ Check power supply (e.g., 1L+)
0x9502 0x1808 Device event overflow Contact device manufacturer
0x9502 0x1809 Backup inconsistency Access outside the memory area
(2048 octets)
0x9502 0x180A Backup inconsistency Eliminate identity error
0x9502 0x180B Backup inconsistency Unspecified error during data stor-
age
0x9502 0x180C Backup inconsistency Eliminate upload error
0x9502 0x180D Parameter inconsistency Eliminate download error
0x9502 0x180E P24 (class B) missing or has under-
voltage
Check power supply
0x9502 0x180F Short circuit on P24 (class B) Check wiring (e.g., 2L+)
0x9502 0x1810 Short circuit on I/Q Check wiring
0x9502 0x1811 Short circuit on C/Q Check wiring
0x9502 0x1812 Overcurrent on I/Q Check load
0x9502 0x6000 Invalid cycle time Check port configuration parame-
ters
0x9502 0x6001 Revision error (incompatible proto-
col version)
Check port configuration parame-
ters
0x9502 0x6002 ISDU batch failed Fix parameter inconsistency
Process Alarms
A process alarm is triggered by an IO-Link device. An IO-Link device sends the “Event
Code” and the “Event Qualifier” of the event to the IO-Link master. The following values
are set in the event qualifier:
TYPE = 1 (Notification)
MODE = 1 (Single shot)
SOURCE = 0 (Device/remote)
The IO-Link master sends this event to the IO controller as a process alarm. The value of
“Channel Error” is 0x9500 for standard events and 0x9501 for manufacturer-specific
events. The IODD of the IO-Link device contains manufacturer-specific events with mes-
sage text.
The following table describes the possible standard events of the IO-Link device.
Table 86: Process Alarms for IO-Link Device Diagnostics
Channel Error
(PROFINET)
Extended
Channel Error
Type
(PROFINET)
Description of the Error Function
on the Connected IO-Link Device
Corrective Action on the Con-
nected
IO-Link Device
0x9500 0x1000 General malfunction IO-Link device reports unknown error
0x9500 0x4000 Temperature error Eliminate overload