Product Manual

Table Of Contents
765-4102/0100-0000 Properties
Product manual | Version: 2.1.0 19
8PORT IOL-B FLD PN DC 24V 2.0A
Circuit High-side driver; no reverse current protection of the
1L+/2L+ output
Self-protection Overcurrent, overload and overtemperature
Voltage drop through high-side path Less than 200mV
Maximum capacitive load 1000μF parallel to 24Ω; 0.1Hz
470μF parallel to 12Ω; 0.1Hz
220μF parallel to 6Ω; 0.1Hz
Maximum inductive load 1.15H / 2A; 0.2Hz; DC13
Diagnostics (1L+, 2L+) Events: overcurrent, overload and overtemperature
4.4.4 Power Supply
Voltage 1L, 2L 24VDC, –25%/+30% (18VDC...31.2VDC)
Voltages above 34V can permanently damage the
product.
Voltages below approx. 10V lead to a product reset.
Undervoltage warning 17.0V (17.5V −3%) ON message,
18V (17.5V +3%) OFF message
Overvoltage warning 32.1V (31.2V +3%) ON message,
30.3V (31.2V −3%) OFF message
Module power consumption 1L: 0.2A (at 24VDC)
2L: 0.1A (at 24VDC)
Power consumption of supply connections Max. 16A; ensure external limitation or use fuses in
the cables
The maximum total current of the device, including
transmission between the power supply connections,
must not exceed 16A for both 1L and 2L individually. If
additional modules are connected to X32 (PWR OUT),
it may be necessary for the maximum total current to
be monitored with external power supply management.
Maximum current: Observe derating as a function of
temperature
Conductor cross-section For UL-compliant use: 2.5 mm
2
Reverse voltage protection Yes
4.4.5 Electrical Safety
Insulation resistance 60VDC
Test voltage 550VAC RMS
Min. creepage distance 0.7mm
Requirements
Use of PELV/SELV power supplies with fault voltage limited to 60VDC.
When SELV power supplies are used: SELV power supplies with supply via the same
network phase
If PELV (Protective Extra Low Voltage) power supplies are used: PELV (Protective Ex-
tra Low Voltage) power supplies with a secondary power supply connection to the
common reference point
4.4.6 Environmental Conditions
Surrounding air temperature (operation) –25°C...+70°C
Surrounding air temperature (storage) –40°C...+80°C