765-1104/0100-0000 Commissioning
Product manual | Version: 2.1.0 109
16DO FLD PN DC 24V 2.0A
Table 56: Device-Specific Configuration Parameters
Node Name Node Class Access Description
VoltageHysteresis Variable Read Voltage hysteresis; unit:
mA
If the voltage exceeds the
limiting value, the voltage
must fall back below the
limiting value by the hys-
teresis to revoke the diag-
nosis.
The OPC UA server provides nodes with configuration parameters for each port. The
path to this node is:
Root > Object > DeviceSet > [device name] > DigitalConnector > Di-
agnostics > PortXX > Configuration
The following table lists port-specific configuration parameters.
Table 57: Port-Specific Configuration Parameters
Node Name Node Class Access Description
OverCurrentPin1, Over-
CurrentPin2, OverCurrent-
Pin4
Variable Read Warning level for current
upper limit on pin 1, pin 2
or pin 4; unit: 1mA
0: monitoring not enabled
UnderCurrentPin1, Under-
CurrentPin2, UnderCur-
rentPin4
Variable Read Warning level for current
lower limit on pin 1, pin 2
or pin 4; unit: 1mA
0: monitoring not enabled
10.2.5.1.3 Read Process Data
The OPC UA server provides nodes with process data. For example, the OPC UA client
can read out the value on pin 2 of a port in the Pin2ProcessData node. The path to this
node is:
Root > Object > DeviceSet > [device name] > DigitalConnector >
PortXX > ProcessData
Note
OPC UA client can only read process output data
The process output data is written by the PROFINET IO-Controller. The OPC UA client
can only read process output data.
The following table lists port-specific process data.
Table 58: Port-Specific Process Data
Node Name Node Class Access Description
Pin2ProcessData Variable Read Process data on pin 2
Pin4ProcessData Variable Read Process data on pin 4