Electrical data
Ratings per IEC/EN 60664-1
Rated voltage (III / 3) 500 V
Rated impulse voltage (III / 3) 6 kV
Rated voltage (III / 2) 630 V
Rated impulse voltage (III / 2) 6 kV
Rated voltage (II / 2) 1000 V
Rated impulse voltage (II / 2) 6 kV
Rated current 41 A
Legend (ratings) (III / 2) ≙ Overvoltage category III / Pollution degree 2
Approvals per UL 1059
Rated voltage UL (Use Group B) 300 V
Rated current UL (Use Group B) 30 A
Rated voltage UL (Use Group C) 150 V
Rated current UL (Use Group C) 30 A
Rated voltage UL (Use Group D) 300 V
Rated current UL (Use Group D) 10 A
Approvals per CSA
Rated voltage CSA (Use Group B) 300 V
Rated current CSA (Use Group B) 30 A
Rated voltage CSA (Use Group C) 150 V
Rated current CSA (Use Group C) 30 A
Rated voltage CSA (Use Group D) 300 V
Rated current CSA (Use Group D) 10 A
Connection data
Connection technology
CAGE CLAMP
®
Actuation type Operating tool
Solid conductor 0.2 … 6 mm² / 24 … 10 AWG
Fine-stranded conductor 0.2 … 6 mm² / 24 … 10 AWG
Fine-stranded conductor with ferrule with plastic collar 0.25 … 4 mm²
Fine-stranded conductor with ferrule without plastic collar 0.25 … 4 mm²
Strip length 11 … 12 mm / 0.43 … 0.47 Inch
Conductor entry angle to the PCB 45 °
No. of poles 1
Total number of connection points 1
Total number of potentials 1
Number of connection types 1
Number of levels 1