The 750-1607 Field Side Connection Module provides both 24V and 0V to the
inputs and outputs in combination with the 8-channel 750-1506 Input/Output
Module (also suitable for 8-channel I/O modules with single conductor
connection) .
This does away with the need for additional rail-mounted terminal blocks.
Pos: 17.2 /Serie 750 (W AGO-I/O-SYSTEM)/Gerä tebeschreibung/Besc hreibung/I/O-Beschreibung/SY/I/O-Beschreibung 750-1607 @ 8\mod_1278418888596_21. doc @ 59151 @ @ 1
The 24V and 0V power is provided to each of the 8 field side CAGE CLAMP
®
connections.
Pos: 17.3 /Serie 750 (W AGO-I/O-SYSTEM)/Gerä tebeschreibung/Besc hreibung/I/O-Beschreibung/Hinweise/Verweis auf Kapitel " Anschlüsse" @ 8\mod_1276 775378035_21.doc @ 57956 @ @ 1
The assignment of the connections is described in the "Connections" section.
Pos: 17.4 /Dokumentatio n allgemein/Glieder ungselemente/- -----Leerzei le------ @ 3\mod_122466275568 7_0.doc @ 24460 @ @ 1
Pos: 17.5 /Serie 750 (W AGO-I/O-SYSTEM)/Gerä tebeschreibung/Besc hreibung/Versor gung/Versorgung 24 V, 0 V über Leistungskontakte Standard @ 3\mod_12264989 74531_21.doc @ 25020 @ @ 1
The I/O module receives the 24V voltage supply for the field level from an
upstream I/O module or from the fieldbus coupler/controller via the power
contacts used as blade contacts. It then provides this potential to subsequent I/O
modules via the power contacts used as spring contacts.
Pos: 17.6 /Serie 750 (W AGO-I/O-SYSTEM)/Wi chtige Erläuterungen/Si cherheitshinwei se/Achtung/Achtun g: Maximaler Strom Leistung skontakte 10 A @ 3\mod_12 26499143500_21.doc @ 25029 @ @ 1
Do not exceed maximum current via power contacts!
The maximum current to flow through the power contacts is 10 A.
Greater currents can damage the power contacts.
When configuring the system, ensure that this current is not exceeded. If
exceeded, an additional potential feed module must be used.
Pos: 17.7 /Serie 750 (W AGO-I/O-SYSTEM)/Gerä tebeschreibung/Besc hreibung/Einsatzber eich/Einsatzber eich 750-xxxx alle Kop pler/Control ler ohne Einschränkung @ 3\ mod_1232541691906_21. doc @ 26522 @ @ 1
The I/O module 750-1607 can be used with all fieldbus couplers/controllers of the
WAGO-I/O-SYSTEM 750.
Pos: 18 /Dokumentati on allgemein/Glieder ungselemente/---Seitenwechsel--- @ 3\mod_1221108045078_0. doc @ 21810 @ @ 1