750-303
1
102
PROFIBUS DP/FMS Fieldbus Coupler
12 Mbaud; digital and analog signals
Data Contacts
Fieldbus
connection
D-Sub
Address
Power jumper contacts
0 V
Supply via
power jumper contacts
24 V
Supply
24 V
0 V
Status
voltage supply
-Power jumper contacts
-System
Address
Configuration
interface
24V
0V
+ +
01
02
RUN
BF
DIA
I/O RUN
I/O ERR
PROFIBUS
x1
0
1
2
3
4
5
6
7
8
9
x10
0
1
2
3
4
5
6
7
8
9
ADDRESS
C
D
B
A
750- 303
W
This buscoupler connects the WAGO-I/O-SYSTEM as a slave to the PROFIBUS
fieldbus.
The buscoupler automatically configures, creating a local process image which
may include analog, digital or specialty modules. Analog and specialty
module data is sent via words and/or bytes, digital data is sent bit by bit.
PROFIBUS stores the process image in the corresponding Master control (PLC,
PC or NC).
The local process image is divided into two data zones containing the data
received and the data to be sent. The process data can be sent via the PROFI-
BUS fieldbus to the PLC, PC or NC for further processing, and received from the
field via PROFIBUS.
The data of the analog modules is stored in the process image which is created
automatically according to the order in which the modules are connected to the
buscoupler. The bits of the digital modules are sent byte by byte and added to
the analog data. If the amount of digital information exceeds 8 bits, the
buscoupler automatically starts with a new byte.
When implementing new installations with PROFIBUS DP, please consider 750-333 Fieldbus Coupler with extended functions (page 104).
Notice: GSD files required
Description
Item No.
Pack.
Unit
PROFIBUS DP/FMS 12 MBd 750-303 1
Accessories
Item No.
Pack.
Unit
GSD files Download: www.wago.com
Miniature WSB Quick marking system
plain 248-501 5
with marking see pages 352 ... 353
Standards and Approvals
Also see "Approvals Overview" in Section 1
Standard EN 50170
Certification PNO
Conformity marking 1
Shipbuilding ABS, BV, DNV, GL, KR, LR, NKK, PRS, RINA
r UL 508
r ANSI/ISA 12.12.01 Class I, Div. 2, Grp. ABCD, T4
4 EN 60079-0, -15
EN 61241-0, -1
I M2 / II 3 GD Ex nA nL IIC T4
System Data
No. of couplers connected to Master 96 with repeater
Max. no. of I/O points approx. 6000 (depends on master)
Transmission medium Cu cable acc. to EN 50170
Max. length of fieldbus segment 100 m ... 1200 m (depends on baud rate/
cable)
Baud rate 9.6 Kbaud ... 12 Mbaud
Transmission time typ. 1 ms (10 couplers; 32 digital I/Os per
coupler at 12 Mbaud) max. 3.3 ms
Buscoupler connection 1 x D-Sub 9; socket
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes 16.05.2012
Postfach 2880 - D-32385 Minden
Hansastr. 27 - D-32423 Minden
Phone: +49(0)571/887-0 E-Mail: info@wago.com
Fax: +49(0)571/887-169 www.wago.com