Datasheet

750-346
1
122
DeviceNet ECO Fieldbus Coupler
125 ... 500 Kbaud; digital and analog signals
Data contacts
DIP switch
for MAC ID
and baud rate
Configuration
interface
Marking area
Status indication
-Fieldbus
-Fieldbus note
Fieldbus
connection
231 Series (MCS)
Supply
24 V
0 V
OVERFL
RUN
BUS OFF
DEVICENET
CONNECT
1 2 3 4 5 6 7 8
ON
NS
MS
01
02 03
04
I/O
750- 346
W
The ECO fieldbus coupler is designed for applications with a reduced scale I/
O requirement. Using digital only process data or small amounts of analogs,
while retaining all of the choice that’s offered by the Series 750 I/O.
The coupler has an integrated supply terminal for the system voltage. The field
power jumper contacts are supplied via a separate supply module.
The DeviceNet
TM
buscoupler automatically configures, creating a local process
image which may include analog, digital or specialty modules.
DeviceNet
TM
stores the process image in the corresponding Master control
(PLC, PC or NC).
The local process image is divided into two data zones containing the data re-
ceived and the data to be sent. The process data can be sent via the Device-
Net
TM
fieldbus to the PLC, PC or NC for further processing, and received from
the field via DeviceNet
TM
.
The data of the analog modules is stored in the process image which is created
automatically according to the order in which the modules are connected to the
buscoupler. The bits of the digital modules are sent byte by byte and added to
the analog data. If the amount of digital information exceeds 8 bits, the
buscoupler automatically starts with a new byte.
Notice: EDS files required
Description
Item No.
Pack.
Unit
DeviceNet ECO 750-346 1
Accessories
Item No.
Pack.
Unit
EDS files Download: www.wago.com
Miniature WSB Quick marking system
plain 248-501 5
with marking see pages 352 ... 353
Approvals
Also see "Approvals Overview" in Section 1
Conformity marking 1
r UL 508
r ANSI/ISA 12.12.01 Class I, Div. 2, Grp. ABCD, T4
4 IEC 60079-0, -15 BR-Ex nA II T4
4 EN 60079-0, -15
EN 61241-0, -1
I M2 / II 3 GD Ex nA nL IIC T4
System Data
No. of couplers connected to Master 64 with scanner
Max. no. of I/O points approx. 6000 (depends on master)
Transmission medium Shielded Cu cable Trunk line:
2 x 0.82 mm² + 2 x 1.7 mm²
Drop line: 2 x 0.2 mm² + 2 x 0.32 mm²
Max. length of bus line 100 m ... 500 m (depends on baud rate/
cable)
Baud rate 125 Kbaud, 250 Kbaud, 500 Kbaud
Buscoupler connection 5-pole male connector, 231 Series (MCS),
female connector 231-305/ 010-000/
050-000 (included)
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes 16.05.2012
Postfach 2880 - D-32385 Minden
Hansastr. 27 - D-32423 Minden
Phone: +49(0)571/887-0 E-Mail: info@wago.com
Fax: +49(0)571/887-169 www.wago.com