Datasheet

750-347
1
130
CANopen ECO Fieldbus Coupler MCS
10 Kbaud ... 1 Mbaud; digital and analog signals
Data contacts
Fieldbus
connection
231 Series (MCS)
Configuration
interface
Marking area
Status indication
-Fieldbus
-Fieldbus note
DIP switch
for node ID
and baud rate
Supply
24 V
0 V
STOP
RUN
TX
CANopen
RX
1 2 3 4 5 6 7 8
ON
I/O
OVERFL
01
02
03
04
750- 347
W
The ECO fieldbus coupler is designed for applications with a reduced scale I/
O requirement. Using digital only process data or small amounts of analogs,
while retaining all of the choice that’s offered by the Series 750 I/O.
The coupler has an integrated supply terminal for the system voltage. The field
power jumper contacts are supplied via a separate supply module.
The CANopen bus coupler is capable of supporting all I/O modules and au-
tomatically configures, creating a local process image.
The local process image is divided into two data zones containing the data re-
ceived and the data to be sent. The process data can be sent via the CANopen
fieldbus to the PLC, PC or NC for further processing, and received from the field
via CANopen.
The data of the analog modules is stored in the PDOs according to the order in
which the modules are connected to the buscoupler. The bits of the digital mo-
dules are sent byte by byte and also mapped in the PDOs. If the amount of di-
gital information exceeds 8 bits, the buscoupler automatically starts with a new
byte.
All entries of the object dictionary can be mapped - as the user likes - in the 5
Rx PDOs and 5 Tx PDOs.
The complete input and output process image can be transmitted using SDOs.
“Spacer modules“ can be set via software.
Note: EDS files required
Description
Item No.
Pack.
Unit
CANopen ECO MCS 750-347 1
Accessories
Item No.
Pack.
Unit
EDS files Download: www.wago.com
Miniature WSB Quick marking system
plain 248-501 5
with marking see pages 352 ... 353
Approvals
Also see "Approvals Overview" in Section 1
Conformity marking 1
Shipbuilding ABS, DNV, GL, KR
r UL 508
r ANSI/ISA 12.12.01 Class I, Div. 2, Grp. ABCD, T4
4 IEC 60079-0, -15 BR-Ex nA II T4
4 EN 60079-0, -15
EN 61241-0, -1
I M2 / II 3 GD Ex nA nL IIC T4
System Data
No. of couplers connected to Master 110
Transmission medium Shielded Cu cable 3 x 0.25 mm²
Max. length of bus line 30 m ... 1000 m (depends on baud rate/
cable)
Baud rate 10 Kbaud ... 1 Mbaud
Buscoupler connection 5-pole male connector, 231 Series (MCS),
female connector 231-305/ 010-000
(included)
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes 16.05.2012
Postfach 2880 - D-32385 Minden
Hansastr. 27 - D-32423 Minden
Phone: +49(0)571/887-0 E-Mail: info@wago.com
Fax: +49(0)571/887-169 www.wago.com