Fieldbus Independent I/O Modules 4 AI DC ±10 V, Single-Ended 750-457 Manual Version 1.0.
ii • General Copyright © 2006 by WAGO Kontakttechnik GmbH & Co. KG All rights reserved. WAGO Kontakttechnik GmbH & Co. KG Hansastraße 27 D-32423 Minden Phone: +49 (0) 571/8 87 – 0 Fax: +49 (0) 571/8 87 – 1 69 E-Mail: info@wago.com Web: http://www.wago.com Technical Support Phone: +49 (0) 571/8 87 – 5 55 Fax: +49 (0) 571/8 87 – 85 55 E-Mail: support@wago.com Every conceivable measure has been taken to ensure the correctness and completeness of this documentation.
Content • iii Content 1 Important Comments ................................................................................. 4 1.1 Legal Principles........................................................................................ 4 1.1.1 Copyright ............................................................................................. 4 1.1.2 Personnel Qualification ....................................................................... 4 1.1.3 Intended Use .....................................
• Important Comments Legal Principles 1 Important Comments To ensure fast installation and start-up of the units described in this manual, we strongly recommend that the following information and explanations are carefully read and abided by. 1.1 Legal Principles 1.1.1 Copyright This manual is copyrighted, together with all figures and illustrations contained therein. Any use of this manual which infringes the copyright provisions stipulated herein, is not permitted.
Important Comments Symbols • 5 1.2 Symbols Danger Always abide by this information to protect persons from injury. Warning Always abide by this information to prevent damage to the device. Attention Marginal conditions must always be observed to ensure smooth operation. ESD (Electrostatic Discharge) Warning of damage to the components by electrostatic discharge. Observe the precautionary measure for handling components at risk.
• Important Comments Safety Notes 1.4 Safety Notes Warning Switch off the system prior to working on bus modules! In the event of deformed contacts, the module in question is to be replaced, as its functionality can no longer be ensured on a long-term basis. The components are not resistant against materials having seeping and insulating properties. Belonging to this group of materials is: e.g. aerosols, silicones, triglycerides (found in some hand creams).
50-457 [4 AI DC ±10 V, Single-Ended] View • 7 2 I/O Modules 2.1 Digital Output Modules 2.1.1 750-457 [4 AI DC ±10 V, Single-Ended] 4-Channel Analog Input Module (± 10 V, Single-Ended) 2.1.1.1 View 13 14 Error AI 1 Error AI 3 A C B D E1 E2 AI 1 Error AI 2 Error AI 4 Datacontacts AI 2 M M Common (ground) Common (ground) E3 E4 AI 3 AI 4 M M Common (ground) 750-457 Common (ground) Power jumper contacts Fig. 2.1.1-1: 4-Channel Analog Input Module 750-457 2.1.1.
• 750-457 [4 AI DC ±10 V, Single-Ended] Display Elements The field side supply voltage of 24 V and 0 V for the input module is derived from adjacent I/O modules or from a supply module. The field supply voltage is passed on separately galvanically to following modules without own use. The supply voltage for the field side is made automatically through the individual I/O modules by means of power jumper contacts. Warning The maximum current of the internal power jumper contacts is 10 A.
750-457 [4 AI DC ±10 V, Single-Ended] Schematic Diagram 2.1.1.4 Schematic Diagram 5 1 AI 1 Common (ground) AI 2 2 6 3 7 A AI D Logic Error 270pF 24V AI 3 0V AI 4 10nF Common (ground) 8 4 750-457 Common (ground) Fig. 2.1.1-3: 4-Channel Analog Input Module 750-457 2.1.1.5 Technical Data Module Specific Data Number of inputs 4 Voltage supply via system voltage DC /DC Current consumption typ. (internal) 65 mA Input voltage max.
• 750-457 [4 AI DC ±10 V, Single-Ended] Technical Data Standards and Regulations (cf. Chapter 2.2 of the Coupler/Controller Manual) EMC-Immunity to interference (CE) acc. to EN 50082-2 (96) EMC-Emission of interference (CE) acc. to EN 50081-1 (93) EMC-Immunity to interference (Ship building) acc. to Germanischer Lloyd (01) EMC-Emission of interference (Ship building) acc. to Germanischer Lloyd (01) Approvals (cf. Chapter 2.
750-457 [4 AI DC ±10 V, Single-Ended] Process Image 2.1.1.6 • 11 Process Image The analog input module 750-457 transmits 16-bit measured values and 8 optional status bits per channel. The digitalized measured value is transmitted in a data word (16 bits) as input byte 0 (low) and input byte 1 (high) into the process image of the coupler / controller. This value is represented with a 12 bit resolution on bit B3 ... B14. The status information included in the three least significant bits (B0 ...
• 750-457 [4 AI DC ±10 V, Single-Ended] Process Image 2.1.1.6.1 Standard Data Format For the standard module 750-457 , the input voltage ranging from –10 V to +10 V is scaled on the numerical values ranging from 0x8000 to 0x7FFF. Process values of module 750-457 Input Numerical value voltage binary hex. dec. Measured value *) X F Ü ± 10 V <-10 '1000.0000.0000.0 X11' 0x8003 -32765 -10 '1000.0000.0000.0 X00' 0x8000 -32768 -8 '1001.1001.1001.1 X00' 0x9998 -26214 -6 '1011.0011.0011.
750-457 [4 AI DC ±10 V, Single-Ended] Process Image WAGO-I/O-SYSTEM 750 I/O Modules • 13
WAGO Kontakttechnik GmbH & Co. KG Postfach 2880 • D-32385 Minden Hansastraße 27 • D-32423 Minden Phone: 05 71/8 87 – 0 Fax: 05 71/8 87 – 1 69 E-Mail: info@wago.com Internet: http://www.wago.