Datasheet

Subject to design changes WAGO Kontakttechnik GmbH & Co. KG Postfach 2880 D-32385 Minden Tel.: +49(0)571 /887-0 E-Mail: info@wago.com
31.07.2006 Hansastr. 27 D-32423 Minden Fax.: +49(0)571 /887-169 www.wago.com
2-Channel Analog Input Module 0-30 V
differential measurement input
Fig. Series 750 / Technical data see page 41 / Delivery without Mini WSB marker
Series 750 / 753 marking see pages 32 ... 33 / 34 ... 35
+AI 2
Data contacts
Error AI 2
-AI 2
Shield
(screen)
Error AI 1
Function AI 1
+AI 1
Shield
(screen)
-AI 1
Function AI 2
+E1 +E2
13
14
C
D
B
A
—E1
—E2
SS
750-483
+AI 2
-AI 2
+AI 1
Shield
(screen)
-AI 1
+AI 2
-AI 2
Shield
(screen)
Logic
A
D
Function
Error
270 pF
270 pF
750-483
1
2
3
4
5
6
7
8
The analog input module receives differential signals of values ± 10 V DC or
0 V ... 30 V.
The input signal of each channel is electrically isolated and will be transmitted
with a resolution of 14 bits.
The internal system supply (via the data bus contacts) is used for the power
supply of the module.
The shield (screen) is directly connected to the DIN rail.
Measured-value acquisition: time synchronous (both inputs)
Overrange / measuring range underflow: status byte and LED
Method of conversion: SAR (Successive Approximation Register)
Operating mode: continuously sampling (preset)
Protection: RC circuit
Description
Item no.
Pack.
unit
2AI 0-30V DC Diff. Measur. Inp. 750-483 1
2AI 0-30V DC Diff. Measur. Inp.
(without connector)
753-483 1
Accessories
Item no.
Pack.
unit
Connectors Connectors Series 753-110 25
Coding elements 753-150 100
Miniature WSB Quick marking system
plain 248-501 5
with marking see pages 224 ... 225
Approvals
Series 750 and 753
r UL 508
Conformity marking 1
Series 750
Marine applications see pages 36 ... 39
Technical Data
No. of inputs 2, electrically isolated from each other
Voltage supply via system voltage DC / DC
Current consumption typ (internal) 80 mA
Signal voltage 0 V ... 30 V
Internal resistance 1 M
Input filter low pass first order, f
G
= 5 kHz
Resolution of the A/D converter 14 bits
Monotonicy without missing codes yes
Resolution of measured value 14 bits
Value of a LSB (least significant bit) 1.8 mV
Measuring error (25°C)
± 0.05 % of the full scale value
Temperature coefficient < ± 0.01 % / K of the full scale value
Measuring error
0.4 % over whole temperature scale
0.1 % of upper range value (non-linearity)
Crosstalk attenuation 80 dB
Sampling time of repetition 1 ms
Sampling delay (module) 1 ms
Sampling delay (channel/channel) 1 μs
Sampling duration 5 μs
Admissible continuous overload 230 V
Voltage resistance
DC 500 V canal / canal or channel /system
Bit width 2 x 16 bits data
2 x 8 bits control / status (optional)
Wire connection CAGE CLAMP
®
Cross sections 0.08 mm² ... 2.5 mm² / AWG 28 ... 14
Stripped length series 750 / 753 8 ... 9 mm / 0.33 in; 9 ... 10 mm / 0.37 in
Width 12 mm
Weight approx. 55 g
EMC 1 -Immunity to interference acc. to EN 50082-2 (1996)
EMC 1 -Emission of interference acc. to EN 50081-1 (1993)
EMC marine appl. - Immunity to interf.
acc. to Germanischer Lloyd (2001)
EMC marine appl. - Emission of interf.
acc. to Germanischer Lloyd (2001)
750-483 / 753-483