Datasheet

750-830
1
86
PLC - BACnet/IP Programmable Fieldbus Controller
32-bit CPU, multitasking
Data contacts
Fieldbus
connection
RJ-45
Fieldbus
connection
RS-232
Power jumper contacts
Mode switch
0 V
Supply via
power jumper contacts
24 V
Supply
24 V
0 V
Status
voltage supply
-System
-Power jumer contacts
Service interface as
configuration and
programming interface
(with cover open)
24V 0V
++
_
01
02
7
50-83
0
LINK
ACT
MS
BT
I/O
BACnet/IP
C
D
B
A
NS
USR
_
The 750-830 BACnet PLC connects the WAGO-I/O-SYSTEM to the BACnet
protocol.
The 750-830 controller corresponds to BACnet B-BC device profile according
to DIN EN ISO 16484-5.
The controller provides the three following functionalities:
1. Native server: For each channel, appropriate BACnet objects are generated
automatically for the digital and analog I/O modules that are connected to the
controller.
2. Application server: Other supported BACnet objects can be created via IEC
-61131-3 programming environment.
3. Application client: Using the client functionality, objects and their properties
can be accessed by other BACnet devices. Access to BACnet/IP networks is
provided by the controller's RJ-45 interface.
The integrated RS-232 interface communicates with external devices. The con-
troller can also be addressed as Modbus RTU slave via RS-232 interface.
Programming PLC applications is performed in compliance with IEC 61131-3.
The controller has a battery-backed RTC and 32-bit multitasking CPU.
For Web-based applications, HTML pages can be generated on an internal ser-
ver.
Start-up and configuration of the BACnet networks is performed using the Win-
dows-compliant WAGO BACnet Configurator.
Description
Item No.
Pack.
Unit
BACnet/IP Controller 750-830 1
Accessories
Item No.
Pack.
Unit
PC softwareWAGO BACnet configurator see page 92
WAGO-I/O-PRO V2.3, RS-232 kit 759-333 1
Miniature WSB Quick marking system
plain 248-501 5
with marking see pages 352 ... 353
Approvals
Also see "Approvals Overview" in Section 1
BACnet approvals
WSPCert certification ISO 16484-5:2010
BTL listing BTL (BACnet
®
Testing Laboratories)
Conformity marking 1
Shipbuilding ABS, DNV, GL, KR
r UL 508
r ANSI/ISA 12.12.01 Class I, Div. 2, Grp. ABCD, T4
4 EN 60079-0, -15
EN 61241-0, -1
I M2 / II 3 GD Ex nA IIC T4
System Data
System data ETHERNET:
No. of controllers limited by network topology
Transmission medium S-UTP 100 Ω Cat 5
Max. length of fieldbus segment 100 m limited by IEEE 802.3
Max. length of network acc. to IEEE 802.3 standard
Baud rate 10/100 Mbit/s
Buscoupler connection RJ-45
Protocols BACnet/IP, MODBUS/TCP (UDP), HTTP,
BootP, DHCP, DNS, SNTP, FTP, SNMP V1,
SMTP
System data Serial:
Transmission medium Shielded Cu cable 2 (4) x 0.25 mm²
Max. length of fieldbus segment 15 m depending on baud rate/cable (at
19200 baud)
Baud rate 9600 baud ... 115 200 baud
Buscoupler connection 1 x D-Sub 9; socket
Programming WAGO-I/O-PRO V2.3
IEC 61131-3 IL, LD, FBD (CFC), ST, FC
BACnet device profile B-BC (BACnet Building Controller)
BACnet-Revision 1.7
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes 16.05.2012
Postfach 2880 - D-32385 Minden
Hansastr. 27 - D-32423 Minden
Phone: +49(0)571/887-0 E-Mail: info@wago.com
Fax: +49(0)571/887-169 www.wago.com