User Manual

WAGO PERSPECTO® 762 Service 45
762-3150/000-003 CP 150 XGA TV CAN
Manual
Version 1.0.2
7 Service
7.1 Battery Maintenance
Do not charge, disassemble or burn the battery!
Incorrect use of the lithium battery contained in this device may cause damage
incurred by fire or chemical burns. The battery must not be charged,
disassembled, burned or exposed to temperatures exceeding 100°C (212°F).
Replace the battery only with an identical one!
Only replace the lithium battery with an identical one. Use of another type of
lithium battery may present a risk of fire or explosion.
Data loss!
If the device is switched off when the battery has failed or has reached its
capacity without replacing the battery, any settings not saved are lost.
The battery in the device control buffers the adjustable parameters and the time
for a power failure or switched off device.
Replace the battery as follows:
1. Make sure that the device has been on for at least 10 minutes before
replacing the battery, allowing the buffer capacitors to load.
2. Switch off the power supply.
3. Remove the buffer battery and install a new one.
4. Restore the power supply.
5. Dispose the discharged battery immediately in a proper manner.
It is possible to check the capacity of the battery via the CODESYS function
SysRtcCheckBattery.