User Manual

Touch Panel Standard Line Properties 45
762-4xxx TP 600
Manual
Version 1.3.0
4.8 Schematic Diagram
NOTICE
Do not use grounded USB devices!
USB interface shielding is not grounded directly, but rather via interference-
suppression capacitors. Only keyboards, mice and USB memory sticks
should be connected to the USB ports. Do not connect devices that are
grounded, e.g., printers, because they bridge the interference-suppression
capacitors, and immunity to interference is reduced.
4.8.1 Schematic Diagram PIO1
Figure 18: Schematic Diagram PIO1