User Manual

120 Commissioning Touch Panel Standard Line
762-4xxx TP 600
Manual
Version 1.3.0
Note the firmware version!
Restoring the controller operating system (“System” selection) is only permissible
and possible if the firmware versions at the backup and restore times are
identical.
If necessary, skip restoring the controller operating system, or match the
firmware version of the controller to the firmware version of the backup time
beforehand.
Restoration only possible from internal memory!
If the device was booted from the memory card, the firmware cannot be restored.
Reset by restore
A reset is performed when the system or settings are restored by CODESYS!
Connection loss through restore
If the restore changes the parameters of the ETHERNET connection, the WBM
may then no longer be able to open a connection to the device. You must call the
WBM again by entering the correct IP address of the device in the address line.
Click the [Browse] button to select the files in Explorer. The buttons only appear
if the network is selected as the data source.
To start the restore procedure, click the [Submit] button.