Manual
Version 1.3.0
4.4.5.2 Operating as an RS-485 Interface
To minimize reflection at the end of the line, the RS-485 line must be terminated
at both ends by a cable termination. If required, one pull-up or pull-down resistor
may be used. These resistors ensure a defined level on the bus when no
subscriber is active, i.e., when all subscribers are in “Tri-state”.
Attention bus termination!
The RS-485 bus must be terminated at both ends!
No more than two terminations per bus segment may be used!
Terminations may not be used in stub and branch lines!
Drop cables must be kept as short as possible!
Operation without proper termination of the RS-485 network may result in
transmission errors.
Figure 16: RS-485 Bus Termination
4.4.6 “X4” CAN Interface
(Only with PIO3 Hardware)
This interface is designed as a D-sub 9 plug and is electrically isolated from the
supply voltage of the device and the other interfaces.
The interface corresponds to ISO 11898-2.