User Manual

72 Mounting Touch Panel Standard Line
762-4xxx TP 600
Manual
Version 1.3.0
6 Mounting
Consider the IP protection type!
The device is an open unit whose back side is IP20 protected, only. If the
operating environment does not fulfill these requirements you have to install the
device into cabinet resp. housing. Then a maximum protection type IP65 can be
achieved depending on the cabinet resp. housing.
Avoid exposure to direct light!
Position the panel to avoid direct exposure to a strong light source, e.g., sunlight!
6.1 Assembly Guidelines/Standards
DIN 60204 Electrical equipment of machines
DIN EN 50178 Electronic equipment for use in power installations
(replacement for VDE 0160)
EN 60439 Low-voltage switchgear and controlgear assemblies
6.2 Installation in Front Door or Housing
The panels are intended for installation that adheres to UL type 1, type 12 or type
4X, e.g., in a control cabinet’s front door or in an appropriate housing. To ensure
adequate cooling and a suitable cable route, a free space of 100 mm must be
available on all sides.
The permitted ambient temperature depends on the mounting position!
If the panel is not installed vertically, cooling is affected, i.e., maximum
permissible ambient temperature is reduced. For exact values, see section
“Device Description” > “Technical Data”.
The panels are mounted from the front of the cabinet into the provided cutout.
Press the panel into the cutout until the four mounting clips audibly engage.
To hold the panel securely in place and to achieve IP65 or a UL-NEMA4 degree
of protection (depending on the cabinet's protection class) you must also screw
the panel from behind into the door using the included 4, 8 or 10 clamping
elements. The following installation drawings must be observed.