4.9.4 Climatic Environmental Conditions
Table 22: Technical Data ‒ Climatic Environmental Conditions
Permissible ambient temperatures
Mounting position
horizontal
or
Mounting position
± 45°
Mounting position
vertical
4.3”
0 … 50 °C
0 … 50 °C
0 … 55 °C
5.7”
0 … 50 °C
0 … 50 °C
0 … 55 °C
7.0”
0 … 50 °C
0 … 50 °C
0 … 55 °C
10.1”
0 50 °C
0 50 °C
0 … 55 °C
Permissible storage temperature
−20 ... +80 °C
Please refer to the chart below.
Relative humidity
(without condensation)
10 ... 90 %
Please refer to the chart below.
Operating altitude
0 … 2000 m
The permissible storage temperature and relative humidity that occurs are
interdependent. The chart below shows the relationship. The permitted range is
shaded in gray.
Example 1:
With relative humidity of 90 %, the device can be stored at a maximum
temperature of 60 °C.
Example 2:
With a storage temperature of 68 °C, the maximum relative humidity can be
60 %.