User Manual

54 Functions Touch Panel Marine Line
762-6xxx/8000-000x TP 600
Manual
Version 1.1.0
The following can be configured as the start page:
the WBM
the selection list “PLC List”/”Browser Favorites”
the Web visualization of a specific controller directly.
See “Favorites” Page in the new WBM for the configuration of the start page.
5.4 Connection Monitoring
If a CODESYS visualization connection is interrupted, an error message is
displayed and the panel automatically attempts to restore the connection
(reconnect) every 10 seconds.
5.5 WBM for Configuration/Parameterization
The Web-Based Management (WBM) provides an interface for configuring or
parameterizing the panel optimized for the touch-sensitive screen. The WBM can
be called up from the panel directly or on the engineering PC.
A detailed description of all available elements and functions is available in
SectionCommissioning”.
5.6 Network
5.6.1 Interface Configuration
The X1 and X2 ETHERNET interfaces of the panel are connected to an internal
3-port switch, whose third port is connected to the CPU. The “Configuration Type”
is set to “DHCP” by default. The TCP/IP settings such as IP address or subnet
5.6.1.1 Operation with Separate Network Interfaces
When operating with separate network interfaces, both ETHERNET interfaces
can be configured and used separately.
Note that the two interfaces still have the same MAC address. Therefore, they
must not be operated in the same network segment.
When switching to operating with separate interfaces, interface X2 is initialized
with the setting values last valid for it. The connections on the X1 interface
persist.
When operating with separate interfaces and fixed IP address, the device can still
be accessed via the interface X2 via the regular IP address.