Insulating tape
NOTICE: Should it be necessary to tap another phase, this must
be done in a different location. To do so, the contact elements
must be unscrewed and brought back to their original position.
Lift contact element to unlock phase selector and select the new
phase.
NOTICE: Do not reuse in the same location of the flat cable.
After removing the module, the contact holes in the flat cable
must be sealed using insulating tape.
Tighten strain relief screw using a screwdriver.Secure supply cable via strain relief housing.Connecting an installation cable to the supply module.
Stripped, solid conductors are simply pushed into unit. Open clamp
via screwdriver to insert stripped, fine-stranded conductors.
Contact is made with the flat cable by tightening the screws.
Observe 1 Nm of tightening torque!
Snapping on transparent protective cover.