Datasheet

12
291
12
WINSTA
®
MINI special
Technical Data
890 / 891 Series
250 V/4 kV/3 â IEC 60664 2- and 3-pole , 4- and 5-pole PCB connectors
400 V/6 kV/3 â IEC 60664 4- and 5-pole
Clearances and creepage distances ≥ 5.5mm
With strain relief ≥ 6.5 mm to accessible surfaces (protection class II)
max. 16 A, depending on conductor size
0.25 … 1mm
2
(22 … 18 AWG , solid, stranded and fine-stranded
1.5 mm
2
(16 AWG), solid and fine-stranded
approx. 1 mΩ contact resistance
approx. 0.25 mΩ contact transition plug/socket
UL (Depending on end-product standard, it may be necessary to use UL-approved
cables with AWG cross-section. These cables are available upon request.), CCA tech-
nique, IEC 61984, LR, GL, DNV
With strain relief housing: IP2xC
(These compact connectors are not designed for use in open, easily accessible areas)
200, without resistive load
100, with resistive load I
N
= 16 A, tested (1.5 mm
2
/16 AWG)
Mating force: approx. 20 … 70 N (depending on number of poles)
Unmating force when unlocked: approx. 20 … 70 N (depending on number of poles)
Retention force when locked: > 80 N
All connectors for fixed installations (snap-in versions for lighting fixtures, devices or all
types of PCBs and distribution cabinets) are factory-equipped with locking levers to en-
sure plugs and sockets are securely locked. Additional locking levers are only required
for “flying leads” (plug/socket).
Connector material
Insulating parts: Polyamide 6.6 V0, halogen-free (except cable)
Contacts: Copper or copper alloy, surface-treated
Clamping spring: Stainless steel (Cr-Ni)
–5°C … +40°C
–35°C … ≤ 85°C
PVC cable for temperatures ≤  70 °C (including halogen-free)
Insulating parts for temperatures ≤ 105 °C
First make/last break ground contacts
upon request
Rated voltage:
Rated current:
Conductor sizes:
Contact resistance:
Approvals:
Protection type:
Mating cycles:
Mating and unmating forces:
(socket and plug)
Locking levers:
Materials:
Processing temperature:
Continuous operating temperature:
General:
Fire load: