Datasheet

787-1001
Switched-Mode Power Supply, 1-Phase
EPSITRON
®
COMPACT Power
L
N
DC+
DC+
DC -
DC -
Primary switch mode power supply unit
Prepared for class II equipment
Natural convection cooling when horizontally mounted
Stage profile, ideal for distribution boards or distribution boxes
Parallel operation, series connection possible
Electrically isolated output voltage (SELV) acc. to EN 60950-1/UL 60950
Description
Item No.
Pack.
Unit
Switched-Mode Power Supply,
12 VDC / 2A
787-1001 1
Technical Data
Input:
Nominal input voltage Vi nom 100 ... 240 VAC
Input voltage range 85 ... 264 VAC; 120 ... 373 VDC
Input voltage derating < 100 VAC: Ia max. 1.5 A
Frequency 44 ... 66 Hz; 0 Hz
Input current Ii 0.6 A at 110 VAC / 0.4 A at 230 VAC
Discharge current 1mA typ.
Inrush current < 30 A, NTC
Mains failure hold-up time > 10 ms at 110 VAC /
> 80 ms at 230 VAC
Output:
Nominal output voltage Vo nom 12 VDC (SELV)
Output voltage range 10.8 ... 18 VDC adjustable
Output current Io 2 A at 12 VDC
0.75 A at 18 VDC
max. 1.4 A (12 VDC) in any mounting
position
Factory preset 12 VDC
Adjustment accuracy 2%
Residual ripple < 150 mV (peak-to-peak) at 20 MHz
Current limitation 1.1 x I
o
typ.
Overload behavior Constant current
Operational indication LED green (V
o
)
Efficiency / power losses:
Efficiency 80 % typ.
Power loss P
V
2.6 W (230 VAC/no load),
6.0 W (230 VAC/rated load)
Max. power loss P
V
6 W typ. (100 VAC / 12 VDC, 2 A)
Fuse protection:
Internal fuse T 2 A / 250 V
External fuse Circuit breakers 10 A, 16 A,
characteristic: B or C
An external DC fuse is required for the DC
input voltage
Technical Data
Environmental requirements:
Ambient operating temperature -25 °C … +60 °C
(UL: -25 °C … +55 °C);
Device start at -40 °C (type-tested)
Storage temperature -25 °C ... +80 °C
Rel. humidity 5 % ... 96 % (no condensation)
Derating -3 % / K (> 45 °C)
Degree of pollution 2 (acc. to EN 50178)
Climatic category 3K3 (acc. to EN 60721)
Safety and protection:
Enclosure Plastic, light gray,
Flammability class V0 acc. to UL94
Test voltage pri. - sec. 4.2 kV DC
Protection class Prepared for class II equipment
Degree of protection IP20 (acc. to EN 60529)
Overvoltage protection < 30 VDC (in the event of a fault)
Short circuit protection yes
No-load proof yes
Feedback voltage max. 20 VDC
Parallel operation yes
Series connection yes
MTBF 500000 h
Connection and type of mounting:
Wire connection Input/Output: WAGO 740 Series
Cross sections Input/Output:
0.08 ... 2.5 mm² / AWG 28 ... 12
Strip lengths Input/Output:
6 ... 7 mm / 0.24 ... 0.28 in
Type of mounting DIN-rail mount (EN 60715)
Dimensions and weight:
Dimensions (mm) W x H x L 54 x 89 x 59
Length: 55 mm, from upper-edge of DIN 35 rail
Weight 180 g
Standards and approvals:
Standards/Specifications EN 60950, EN 61204-3,
UL 60950, UL 508, GL
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes
14.01.2015
Postfach 2880 - D-32385 Minden
Hansastr. 27 - D-32423 Minden
Tel.: +49(0)571/887-0 E-Mail: info@wago.com
Fax: +49(0)571/887-169 www.wago.com

Summary of content (1 pages)