Datasheet
787-1628
Switched-Mode Power Supply, 1-/2-Phase
EPSITRON
®
CLASSIC Power
L1 (L)
L2 (N)
DC+
DC+
DC -
DC -
DC O.K.
• Primary switch mode power supply unit with TopBoost, enabling secondary-
side protection via electronic circuit breakers
• Suitable for protection class I equipment
• Natural convection cooling when horizontally mounted
• Enclosed for use in switchgear cabinets
•DC OK contact
• Suitable for both parallel and series operation
• Electrically isolated output voltage (SELV) acc. to EN 60950-1/UL 60950-1
Description
Item No.
Pack.
Unit
Switched-mode power supply,
24 VDC/ 5 A
787-1628 1
Technical Data
Input:
Nominal input voltage V
i nom
1 x (2 x) AC 200 … 500 VAC
Input voltage range 180 … 550 VAC; 254 … 780 VDC
Input voltage derating -0.5 % (< 200 VAC)
Frequency 44 Hz … 66 Hz; 0 Hz
Input current I
i
1.25 A (200 VAC);
0.67 A (500 VAC)
Power factor ≥ 0.52
Inrush current < 30 A, NTC
Mains failure hold-up time 126 ms (500 VAC);
15 ms (200 VAC)
Output:
Nominal output voltage V
o nom
24 VDC (SELV)
Output voltage range 23 V … 28.5 VDC adjustable
Factory preset 24 VDC
Output current I
o
5 A at 24 VDC
Adjustment accuracy < 1 %
Residual ripple 30 mV (peak-to-peak) typ.
Current limitation 1.1 x I
o
typ.
Overload behavior Constant current
Operational indication Green LED (V
o
)
Signaling DC OK contact;
Make contact (max. 30 V / 1 A)
Efficiency/Power losses:
Efficiency 89 % typ.
Power loss P
V
0.94 W (no load);
16.36 W (230 VAC, nominal load)
14.55 W (400 VAC, nominal load)
Max. power loss P
V
18.2 W (200 VAC / 24 VDC, 5 A)
Fuse protection:
Internal fuse T 3.15 A / 250 V
External fuse Circuit breakers 6 A, 10 A, 16 A,
characteristic: B or C
An external DC fuse is required for the DC
input voltage
Technical Data
Environmental requirements:
Ambient operating temperature -25 °C … +70 °C;
Device start at -40 °C type-tested
Storage temperature -25 °C … +85 °C
Relative humidity 5 % ... 96 % (no condensation permissible)
Derating -2.5 %/K (> 55 °C)
Safety and protection:
Test voltage PRI–SEC 4.2 kV DC
Protection class Prepared for class I equipment
Degree of protection IP20 (acc. to EN 60529)
Overvoltage protection Varistor (input side);
internal protective circuit,
< 40 VDC (output side in case of an error)
Short circuit protection yes
No-load proof yes
Feedback voltage max. 35 VDC
Parallel operation yes
Series connection yes
Connection and mounting type:
Wire connection Input/Output/Signaling:
WAGO 721 Series
Cross sections Input/Output/Signaling:
0.08 mm² … 2.5 mm² / 28 … 12 AWG
Strip lengths Input/Output/Signaling:
8 … 9 mm / 0.31 … 0.35 in
Mounting type DIN-rail-mount (EN 60715)
Dimensions and weight:
Dimensions (mm) W x H x L 42 x 127 x 137
Length from upper-edge of DIN-rail
Weight 600 g
Standards and specifications:
Standards/Specifications EN 60950-1, EN 61204-3,
UL 60950-1, UL 508, GL*
(* pending)
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes
26.03.2015
Postfach 2880 - D-32385 Minden
Hansastr. 27 - D-32423 Minden
Tel.: +49(0)571/887-0 E-Mail: info@wago.com
Fax: +49(0)571/887-169 www.wago.com