Datasheet

787-1644
Switched-Mode Power Supply, 3-Phase
EPSITRON
®
CLASSIC Power
DC+
DC+
DC -
DC -
DC O.K.
L1
L2
L3
Primary switch mode power supply unit with TopBoost, enabling secondary-
side protection via electronic circuit breakers
Suitable for protection class I equipment
Natural convection cooling when horizontally mounted
Enclosed for use in switchgear cabinets
•DC OK contact
Suitable for both parallel and series operation
Electrically isolated output voltage (SELV) acc. to EN 60950-1/UL 60950-1
Description
Item No.
Pack.
Unit
Switched-mode power supply,
24 VDC/ 40 A
787-1644 1
Technical Data
Input:
Nominal input voltage V
i nom
3 x (2 x) AC 400 … 500 VAC
Input voltage range 320 V … 575 VAC; 450 V … 800 VDC
Frequency 47 Hz … 63 Hz; 0 Hz
Input current I
i
3 x 2.15 A (400 VAC);
3 x 1.82 A (500 VAC)
Inrush current < 30 A, NTC
Mains failure hold-up time 25 ms (500 VAC);
15 ms (400 VAC)
Output:
Nominal output voltage V
o nom
24 VDC (SELV)
Output voltage range 23 V … 28.5 VDC adjustable
Factory preset 24 VDC
Output current I
o
40 A at 24 VDC
Adjustment accuracy < 1 %
Residual ripple 30 mV (peak-to-peak) typ.
Current limitation 1.1 x I
o
typ.
Overload behavior Constant current
Operational indication Green LED (V
o
)
Signaling DC OK contact;
Make contact (max. 30 V / 1 A)
Efficiency/Power losses:
Efficiency 92 % typ.
Power loss P
V
4.2 W (no load);
83.9 W (400 VAC. nominal load)
Max. power loss P
V
83.9 W (500 VAC / 24 VDC, 40 A)
Fuse protection:
Internal fuse -
External fuse 3 x circuit breakers 10 A, 16 A,
B or C characteristic;
or motor circuit breakers
An external DC fuse required for DC input
voltage
Technical Data
Environmental requirements:
Ambient operating temperature -25 °C … +70 °C;
Device start at -40 °C type-tested
Storage temperature -25 °C … +85 °C
Relative humidity 5 % ... 96 % (no condensation permissible)
Derating -2.5 %/K (> 55 °C)
Safety and protection:
Test voltage PRI–SEC 4.2 kV DC
Protection class Prepared for class I equipment
Degree of protection IP20 (acc. to EN 60529)
Overvoltage protection Varistor (input side);
internal protective circuit,
< 40 VDC (output side in case of an error)
Short circuit protection yes
No-load proof yes
Feedback voltage max. 35 VDC
Parallel operation yes
Series connection yes
Connection and mounting type:
Wire connection Input/Signaling: WAGO 721 Series
Output: WAGO 831 Series
Cross sections Input/Signaling:
0.08 mm² … 2.5 mm² / 28 … 12 AWG
Output:
0.5 mm² … 10 mm² / 20 … 8 AWG
Strip lengths Input/Signaling:
8 … 9 mm / 0.31 … 0.35 in
Output: 13 … 15 mm / 0.51 … 0.59 in
Mounting type DIN-rail-mount (EN 60715)
Dimensions and weight:
Dimensions (mm) W x H x L 126 x 127 x 198
Length from upper-edge of DIN-rail
Weight 2800 g
Standards and specifications:
Standards/Specifications EN 60950-1, EN 61204-3,
UL 60950-1, UL 508, GL*
(* pending)
WAGO Kontakttechnik GmbH & Co. KG
Subject to design changes
26.03.2015
Postfach 2880 - D-32385 Minden
Hansastr. 27 - D-32423 Minden
Tel.: +49(0)571/887-0 E-Mail: info@wago.com
Fax: +49(0)571/887-169 www.wago.com

Summary of content (1 pages)