User manual

EPSITRON® Device Description 13
787-1662 Electronic Circuit Breaker
Manual
Version 1.0.0
Pos: 17 /A ll e Ser ien (Al lg emei ne M od ule)/ Üb ers chrif te n für al le S eri en/G erä teb esc hrei bu ng/G erä tebe schr eib ung - Üb ersc hrift 1 @ 3\ mod_1233756084656_21.docx @ 27096 @ 1 @ 1
3 Device Description
Pos: 18.1 /S erie 78 7 (E PSI TRON )/ Ger äteb esc hrei bung / Besc hrei bung /A nwe ndu ng/A nw end ung 787-1662 @ 17\mod_1385383457641_21.docx @ 138285 @ @ 1
The 787-1662 electronic circuit breaker reliably protects up to 2 load circuits
against short circuiting and overloading. The 24 VDC input voltage is distributed
among 2 output channels, each of which can be provided with separate fuse
protection.
Table 4: Fuse Protection of Output Channels
Variant
Fuse protection for each output
channel (can be set)
787-1662
2 A, 3 A, 4 A, 6 A, 8 A, 10 A
787-1662/0106-0000
1 A, 2 A, 3 A, 4 A, 5 A, 6 A
787-1662/0006-1000
0,5 A, 1 A, 2 A, 3 A, 4 A, 6 A
(with active current limitation)
The electronics can accommodate brief current peaks.
Pos: 18.2 /S erie 78 7 (E PSI TRON )/ Ger äteb esc hrei bung / Besc hrei bung /F un ktion /Fu nkt ion 787- 1662 : Drehsc hal ter @ 17\ mod_1385383519243_21.docx @ 138289 @ @ 1
There are 2 rotary switches on the device which can be used to set the nominal
current for each of the individual output channels.
Pos: 18.3 /S erie 78 7 (E PSI TRON )/ Ger äteb esc hrei bung / Besc hrei bung /L ED-A nzeig e/L ED-A nzeig e 787- 16xx @ 12\mod_1342431879376_21.docx @ 100301 @ @ 1
The current status of the output channel is indicated by a multi-colored LED.
Pos: 18.4 /S erie 78 7 (E PSI TRON )/ Ger äteb esc hrei bung / Besc hrei bung /F un ktion /Fu nkt ion 787- 16xx: Kurzsc hluss und Ü berlast @ 13\mod_1342432174185_21.docx @ 100307 @ @ 1
In the event of a short circuit or overloading, the individual output channel is de-
energized after a defined trip time.
Pos: 18.5 /S erie 78 7 (E PSI TRON )/ Ger äteb esc hrei bung / Besc hrei bung /A nwe ndu ng/H in weis e/Hi nw eis: Ther mi sc he E ntspa nnu ng abw art en 7 87-16xx @ 12\mod_1342431732847_21.docx @ 100298 @ @ 1
Wait for temperature to return to normal!
If an output channel has been de-activated due to short-circuiting or overloading,
wait until the temperature returns to its normal range (cooling period) before re-
activating the channel.
Pos: 18.6 /Serie 787 (EPSIT RON)/ Gerät ebesc hrei bung/ Beschr eibung /Fu nkti on/Fun ktio n 787-16xx: Signalkontakte @ 13\mod_1342433022224_21.docx @ 100310 @ @ 1
The device contains control and signaling contacts, which can be used for reading
out information relevant to operation. These contacts are also used to activate and
de-activate specific output channels individually. This device is equipped with
one digital control input and
two digital signal outputs.
Pos: 19 /Doku ment ation all gemei n/Gli eder ungsel eme nte/---Seit en wechs el--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1