6.4 Operating Statuses, Signaling, Reactions
Table 19: Operating statuses, signaling, reactions
Status
Operating status
Channel
LED
Signal output
S3 (common
signal)
Button is
pressed
Transition
to …
Control input S1
Transition
to …
0
Device
initialization.
1
off
off
0 V
-
-
1
Output activated,
function OK.
on
Green
24 V
Status 3
Status 3
(via bit pattern)
2
Output current
greater than
nominal current.
2
on
Green
flashing
24 V
Status 3
Status 3
(via bit pattern)
3
Output de-
activated
manually, or by
control input S1.
3
off
Red
24 V
Status 1
Status 1
(via bit pattern)
4
Output de-
activated due to
excessive current.
Cooling (waiting)
period is active.
4
off
Red
flashing
0 V
-
-
5
Output de-
activated due to
excessive current.
Cooling (waiting)
period is
completed.
5
off
Orange
flashing
0 V
Status 3
Status 1
(using pulse
longer than 0.5 s)
6
Device error:
Defective fuse
detected.
off
Red
flashing,
rapid
0 V
Status 6
-
1
The outputs are re-activated based on the load applied as soon as device initialization is
concluded.
2
The output is de-activated automatically in accordance with the given trip curve. The
device then switches to Status 4.
3
The status is saved when the device is switched off.
4
After a defined waiting period (cooling time), the output switches to Status 5. The
remaining time of the waiting period is saved when the device is switched off. This time
must first elapse when the device is switched on again. This feature protects the switching
elements against any overloading.
5
The output can be re-activated as follows:
by pressing the associated button twice, or
by applying a pulse at control input S1.
The device then switches to Status 1.