User manual

36 Function Description EPSITRON®
787-1662 Electronic Circuit Breaker
Manual
Version 1.0.0
Pos: 55 /S eri e 7 87 ( EPS ITR ON)/F u nkti ons besc hr eibu ng/Z usc hal tver zög eru ng 787- 166x @ 12\mod_1341479703716_21.docx @ 98963 @ 2 @ 1
6.5 ON Delay for Specific Channels
The outputs are activated in a staggered manner in the order of their channel
numbers as soon as a minimum input voltage is present. Outputs which have been
de-activated manually, or by a reset signal, are skipped in this process.
The time at which the next output in the sequence is activated is based on the
following conditions:
At least 50 ms must elapse after activation of the previous output.
The output current of the previously activated output must lie below the
nominal value set for the output.
Pos: 56 /Doku ment ation all gemei n/Gli eder ungsel eme nte/---Seit en wechs el--- @ 3\mod_1221108045078_0.docx @ 21810 @ @ 1