Data
Technical Data
Input
Phases 1
Nominal input voltage U
i nom
AC110 … 240V
Input voltage range AC100 … 264V
Nominal mains frequency range 47 … 63Hz
Input current I
i
≤0.55A (110 VAC);≤0.33A (240 VAC)
Inrush current ≤24A (NTC)
Mains failure hold-up time ≥95ms (230 VAC)
Output
Nominal output voltage U
o nom
DC24V (SELV)
Nominal output current I
o nom
1.25A (24 VDC)
Nominal output power 30 W
Adjustment accuracy ≤2%
Residual ripple ≤60mV (peak-to-peak)
Overload behavior Hiccup