Data Sheet

Data sheet | Item number:788-384
www.wago.com/788-384
06.12.2018Page /2 10
Per EN 50205, it is only permitted to use 1 make contact / 1 break contact for safety circuits (11-14 and 22-21 or 12-11 and 21-24).
Reinforced insulation between coil and contacts
A separator plate (e.g., 209-191) must be used for voltages greater than 250 V between adjacent relay modules and for compliance with the
reinforced insulation requirements.
To protect the relay coils and contacts, inductive loads must be dampened with an effective protection circuit.
Data
Technical Data
Control circuit
Nominal input voltage U
N
24 VDC
Input voltage range -15 … +10 %
Nominal input current at U
N
31 mA
Load circuit:
Number of changeover/switchover contacts 2
Contact material (relay) AgNi
Limiting continuous current 6 A
Max. make current (resistive) 4 s 14 A (AC)
Max. switching voltage 250 VAC
Max. switching power (resistive) 1500 VAAC; DC see load limit curve
Switching capacity AC-15: 3 A / 250 VAC; DC-13: 3 A / 24 VDC
Recommended minimum load 5 V / 10 mA
Pull-in time (typ.) 10 ms
Drop-out time (typ.) 4 ms
Electrical life (N.O.; resistive load; 23 °C)
100 x 10 switching operations
3
Mechanical life (N.O.; resistive load; 23 °C)
10 x 10 switching operations
6
Max. switching load with load/without load
6 min / 300 min
-1 -1
Signaling
Status indication LED red
Safety and protection:
Rated voltage 250 V
Rated impulse voltage 4 kV
Pollution degree 3
Dielectric strength, control/load circuit (AC, 1 min) 4 kV
rms
Dielectric strength, control/load circuit (AC, 1 min) 4 kV
rms
Dielectric strength open contact (AC, 1 min) 1.5 kV
rms